devlog
A 3D model of a liquid-cooling plant with four chillers, nine CDUs and three pods of racks, beside a chart of chiller plant power against ambient that stays flat at about 220 kW until 21.3 °C and then climbs

Solve for the flow, don't prescribe it

17 September 2026 · sd-dc · sinkers/sd-dc

SD-DC had its first commit on 8 September: a toolkit for data centre design led by AI agents. The bet is in the README's first diagram: a brief goes in, an agent calls tools for sizing, routing, costing, CFD and CAD, a model of the building comes out, and every answer is checked by running it. If a check fails, the agent goes round again. That's the design loop.

Most of that loop isn't built. Cable sizing to AS/NZS 3008 is mature. The other tools exist as code but aren't services an agent can call yet, and costing and layout aren't written. This post covers the first ten days: a liquid-cooling model, a viewer for it, and some plumbing that makes the loop more than a sketch.

Flow is an output

The air-side CFD in the repo puts a fixed mass flow on its fan walls. That's right for a steady design-point study. It's no use for asking what happens when a valve shuts, because a prescribed flow can't redistribute.

So the liquid model (hydraulics.py) solves for every flow. Pipes are Darcy–Weisbach, valves get their resistance from a characteristic at a given lift, pumps have a head curve, and every node balances. Newton solves branch flows and node pressures together.

The test that proves it shuts one of four identical rack branches and tells nothing else to change:

net.branch("rack1").valves()[0].position = 0.0
shut = solve(net, base.as_array(net))
assert shut.converged

# The survivors gain - the whole point. Nothing told them to.
assert shut.flow("rack2") > base_each

# Total falls, but by less than the quarter that was removed, because the
# pump rides up its curve as the system resistance rises.
lost = 1.0 - shut.flow("pump") / base.flow("pump")
assert 0.0 < lost < 0.25

(test_hydraulics.py L129–151)

Total flow falls 23.7 %, not 25 %, and each of the other three racks gains 1.6 %. Nobody wrote that behaviour in. It comes from solving the network.

Three things only showed up when tests failed. A shut valve has to be a large finite resistance, because infinite makes the Jacobian singular. A quadratic pump curve through three ordinary datasheet points peaks half a metre above shutoff, and that half-metre put the solver into a two-point limit cycle, so the curve is now clipped monotonic. And a step clamp caused the cycle, so the step is now globalised by backtracking.

Numbers nobody chose

Every parameter sits in loop_params.json with its source and a confidence grade. params.py raises PendingReference rather than fill in a default. A default would be a number nobody chose, and downstream you can't tell it from one somebody did. At the start 24 values were null, including every temperature.

RD110, and its chillers

Schneider's RD110 rev 3, a 10 MW reference design for GB300 racks, settled the temperatures: facility water 37/47 °C, cold plates 40/50 °C. Six nulls closed and the tests written to fail on its arrival did fail.

The surprise was that RD110 doesn't use dry coolers, which is what I was modelling for. It uses four Uniflair XRAF4242A free-cooling chillers, N+1. I first wrote that up as an argument against dry coolers. A commit later I had it the wrong way round. Below some ambient those chillers are dry coolers, fans only. Above it the compressors make up what the coil can't take. chiller.py works out the crossover rather than assuming it:

def crossover_ambient_c(self, load_kw: float, return_water_c: float) -> float:
    return return_water_c - load_kw / self.ua_free_kw_per_k

At RD110's liquid load of 5,930 kW that's 21.3 °C. A fully loaded plant loses free cooling at a lower ambient than a half-loaded one. Plant power goes from 218 kW at 10 °C to 1,375 kW at 42 °C, a factor of 6.3. The coil size, fan power and COP curve behind those numbers are my judgement, not RD110's, and the code says so.

What showing the flow caught

The plant is laid out in one file, layout.py, with no FreeCAD or numpy in it. The FreeCAD STEP export, the browser viewer and the solver all read it, so the pipes you see are the pipes the solver puts flow through: 4 chillers, 9 CDUs, 48 racks, 148 runs over 598 m.

The loop viewer with pipes coloured by velocity against a 3 m/s ceiling, beside panels of loop temperatures, circuit flows, CDU flow meters and chiller power
The loop viewer, pipes coloured by velocity. Every number in the side panels comes from the solved network.

Once flows were on screen, three of my mistakes showed:

  1. 8.5 m/s in the facility mains. RD110's only pipe size callout is DN150 and I'd used it for the mains as well as the branches. Sizing on velocity gives DN300, and the facility pump went from 42.9 m and 30 kW to 23.0 m and 16.8 kW, a 44 % cut.
  2. A tripped CDU ran backwards. With its pump off and no non-return valve, the solver drove −62 m³/h through the dead plate. Correct for the network as drawn, nonsense as a plant. CheckValve exists because of it.
  3. Losing a pump appeared to increase flow. I'd reported circuit flow as one pump's flow times the count. With one pump off the survivors ride up their curves, and it read 193 kg/s against a 152 kg/s design.

In the next commit I fixed my own heat exchanger maths too. I'd calibrated the CDU plate on the 3 K terminal approach, where effectiveness-NTU wants the 13 K inlet-to-inlet difference. That asked for an effectiveness of 3.33. hx.py now raises on anything outside 0 to 1, which is how it surfaced.

The viewer is static: HTML, one JS module, a 0.6 MB geometry bundle and a manifest of solved hydraulics. No service to run.

The rest of the loop

On the cable side, trefoil formation was already in the engine but no caller could reach it. Every request fell back to a guess and warned about it. It's now a stated input on both sizing tools, and the response says which formation it used. The MCP server only spoke stdio, which a hosted client can't start, so http_mcp_server.py serves the same handler over HTTP. There's one implementation of the answer, so the two can't disagree.

Finally, the README now names IndustroML as the model in the middle of the loop: containers, assets, interfaces and connections in one schema. A connection that carries a route through named trays is an electrical fact, a geometric fact and a line on a bill of materials at once, which is what lets one tool hand a length to the next.

What doesn't work yet

The liquid model is Phase 1 of 6: hydraulics, no thermal transport, so a starved rack reports "starved" rather than a temperature. Every run in the layout is straight or one right angle, so fitting losses are a floor. The pipe router came later for that. The suite at the end of the period was 137 liquid-twin tests, all green. The code is MIT on GitHub.

More articles

Grid, BESS and UPS as drop-in components
SD-DC gained power-sim: electrical components that wire together from a model, and a first simulation of a GPU load behind a UPS with a BESS beside it. On a recorded NSW spike day it saves $1,724; on a flat price it loses $8. Neither number is verified against real plant yet.
14 Oct 2026 · sd-dc · 5 min read
A pipe router that says why it can't
SD-DC now routes chilled-water pipes and cable trays as agent services. On a real 34-pipe design it matches the hand routing and comes in 2 m shorter, and when a route can't be built it explains why.